Vibration in an Industrial Ventilation Fan

Defeating unscheduled shutdowns in critical ventilation fans. We solved chronic vibration failure caused by corrosion and dust imbalance, achieving a 1760% ROI. Maintenance reduced to 1 stop per year.
Vibration in an Industrial Ventilation Fan

CHALLENGE

Issue: Unscheduled shutdowns due to bearing vibration failure result in production losses and increased maintenance costs.

Goals:

  • Reduce dust attachment to fan blades and resulting imbalance and vibration
  • Extend bearing life and MTBR
  • Control corrosion and abrasion

Root Cause: High humidity atmosphere with chlorides corrodes fan blades and accelerates dust attachment, creating fan imbalance

SOLUTION

Preparation:

  • Decontaminate to remove chlorides
  • Dynamic balancing of fan
  • Grit blast to Sa 2.5 with 3 mil angular profile

Application:

  1. Apply ARCOR 8507 @ 120 mil (3 mm) to leading edge of vanes
  2. Apply ARCOR S20 @ total DFT of 20 mil
  3. Fan is statically balanced

Results:

  • Shutdowns reduced to 1 per year at cost of $25,000
  • Bearing life extended due to reduced vibration

ESTIMATED SAVINGS:

  • Shutdowns reduced to 1 per year at cost of $25,000
  • Bearing life extended due to reduced vibration
  • Annual savings more than 18x repair cost

ROI = 1760%